8-51
IM 05P01C31-01EN
Control Functions
n
Heating/coolingLoopControlwithPVAuto-selector(2inputs)FunctionBlockDiagram
Target setpoints 1 to 8
COM
LOCALREMOTE
SP ramp rate
SP limiter
DI16PV
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias
PV input filter
Ratio bias computation
PV auto-selector (Max., Min., Ave., Diff.)
A.BS
A.FL
BS
FL
PMD An, Bn
10-seg. linearizer approx./bias
PMD An, Bn
10-seg. linearizer approx./bias
PMD An, Bn
PV.AS
P.UNI P.DP P.RH, P.RL
CNT ALG
UPR, DNR TMU
SPNO SP
R/L
SPH, SPL
A.SR A.LC
UNIT
IN
RH, RL
SDP
SH, SL
RSP
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
A.BS
A.FL
A.SR A.LC
UNIT
IN
RH, RL
SDP
SH, SL
DI3DI1 DI2
Control computation
Manual operation
Manual preset output
Input error preset output
Heating-side preset output
AUTO (ON)/MAN (OFF) switch
STOP (ON)/RUN (OFF) switchSTOP (ON)/RUN (OFF) switch
AUTO
When sensor
burnout occurs
Normal Normal
MAN
RUNSTOP
EPO
OH, OL OHc, OLc
Error preset output
When sensor
burnout occurs
EPO
PO
Cooling-side preset output
STOP
POc
S/R
MPON
Heating/cooling computation
Heating-side output limiter Cooling-side output limiter
RUN
Relay Relay
LPS
24 V loop
power supply
Current
OUT retransmission output OUT2 retransmission output
OT
O1RS O2RS
RET retransmission output
RTS
Heating-side
output
Heating-side
output
OUTOUT
Cooling-side
output
Cooling-side
output
OUT2 OUT2 RET AL3AL2AL1
Output terminal assignment
PMD
OU.H OU.L OU2.H OU2.L
An, Bn PMD An, Bn
Split computation
10-seg. linearizer approx./bias
Split computation
10-seg. linearizer approx./bias
RET.H RET.L
PMD An, Bn
Split computation
10-seg. linearizer approx./bias
Alarm
Equipped as standard Equipped as standard
A/M
No function
is assigned
to DI3 and
DI16.
PV input 1 PV input 2
Aux. analog (remote) input (E1-terminal area)
Contact inputs
Equipped as standard
For the model with optional suffix code /DR:
Remote input with direct input (E1-terminal area)
can be used when
UT55A suffix code: Type 2 = 1, 2, 4, 5, or 7 and
with optional suffix code /DR;
UT52A suffix code:Type 2 = 1 or 2 and
with optional suffix code /DR.
However, DI16 is to be deleted.
Alarm 1
(PV high limit)
Alarm 2
(PV low limit)
Alarm 3
(PV high limit)
Terminal Parameter Function
Analog signal Contact signal Front panel key
Legend
* After the control output terminal is specified by the parameter OT,
other current output terminals can be used as retransmission output.
Current or
voltage pulse
(Current when retransmission output)
Current or
voltage pulse
(Current when retransmission output)
Sensor burnout occurs when PV or RSP
input burnout occurs.
However, burnout is not detected if input
is not conncted.
PV display
SP display
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
Manual output is prioritized even if
sensor burnout occurs in MAN.
RMS
*1: RS-485, Ethernet, PROFIBUS-DP,
DeviceNet, CC-Link
Universal input (E1-terminal area) can be used
when UT55A/UT52A optional suffix code /U1.
However, DI16 does not exist.
(For Standard model)
UT55A suffix code: Type 2 = 1, 2, 4, 5, or 7;
UT52A suffix code: Type 2 = 1 or 2 is necessary.
(For Detailed model)
UT55A/UT52A optional suffix code /R1 or /RCH1
is necessary.
(For Standard model)
DI16 is equipped when UT55A suffix code: Type 2 =
1, 2, 4, 5, or 7; UT52A suffix code: Type 2 = 1 or 2.
(For Detailed model)
DI16 is equipped when UT55A/UT52A optional
suffix code /R1 or /RCH1.
8
8.1SettingControlMode(CTLM)