EasyManua.ls Logo

YOKOGAWA UT55A - Page 285

YOKOGAWA UT55A
476 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11-10
IM 05P01C31-01EN
FaultdiagnosisAlarm
The function outputs an alarm signal in the following cases.
Thecorrespondingevent(EV)lampislitandthecontactoutputturnson(whenthe
contacttypeisenergized).
• BurnoutofPVinput,RSPremoteinput,orauxiliaryanaloginput
ADC failure ofPVinput,RSPremoteinput,orauxiliaryanaloginput
• Referencejunctioncompensation(RJC)errorofPVinput,RSPremoteinput
The fault diagnosis alarm does not work the stand-by action functions.
FAIL output
When the FAIL condition is caused (faulty MCU or system data error), DO (alarm output)
turned off regardless of contact type.
TheFAILoutput
doesnotworkthealarmlatch,theenergized/de-energizedandthe
stand-by action functions.
Stand-byAction
The stand-by action is a function for ignoring the alarm condition and keeps the alarm off
until the alarm condition is removed. Once the alarm condition is removed, the stand-by
action is cancelled.
It is effective in the following cases where;
The power is turned on
SP is changed
SP number is switched (however, except for remote setpoint) (The SP must be
changed.)
The alarm type is changed
Forced stand-by via communication
The following shows the behavior of an alarm with the stand-by action at power ON.
Treated
as normal
ºC
Power-on
Time
The alarm output does not turn on
in this region even if the PV valule
is below PV low limit alarm setpoint.
PV low limit alarm setpoint
Normal Abnormal
The alarm output
turns on.
11.1SettingAlarmType

Table of Contents

Related product manuals