TuningMenu(Menu:TUNE)(Continuedfrompreviouspage)
Parameter
symbol
Name
Display
level
Setting range Initialvalue
MPON
Manual preset
output number
selection
STD
OFF: Hold the control output in
AUTO mode (bumpless)
1: Use manual preset output 1
(output bump)
2: Use manual preset output 2
(output bump)
3: Use manual preset output 3
(output bump)
4: Use manual preset output 4
(output bump)
5: Use manual preset output 5
(output bump)
OFF
MPO1to
MPO5
Manual preset
output 1 to 5
STD -5.0
to105.0%
 0.0%
In Cascade control, the following parameters are also displayed for secondary loop. (the LP2 lamp
is lit)
• Parameter: MPON, MPO1 to MPO5
ZoneControlMenu(Menu:ZONE)
Parameter
symbol
Name
Display
level
Setting range Initialvalue
RP1 to RP7
Reference point 1
to 7
STD
0.0to100.0%
ofPVinputrange
(EU)
(RP1≤RP2≤RP3≤RP4≤RP5≤
RP6≤RP7)
100.0%ofPV
input range
RHY
ZonePIDswitching
hysteresis
STD
0.0to10.0%
ofPVinputrange
span (EUS)
0.5%ofPV
input range
span
RDV Reference deviation STD
OFF: Disable
0.0+1
digitto100.0%ofPVinput
range span (EUS)
OFF
In Cascade control, the following parameters are also displayed for secondary loop. (the LP2 lamp
is lit)
•Parameter:RP1
toRP7,RHY,RDV
PParameterMenu(Menu:PPAR)
Parameter
symbol
Name
Display
level
Setting range Initialvalue
P01 to P10
P01 to P10
parameter
STD
-19999 to 30000 (Set a decimal
point position using LL50A
Parameter Setting Software.)
0
18.2ListofParameters