EasyManuals Logo

YOKOGAWA UT55A User Manual

YOKOGAWA UT55A
476 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #429 background imageLoading...
Page #429 background image
18-18
IM 05P01C31-01EN
PVInputSettingMenu(Menu:PV)(Continuedfrompreviouspage)
Parameter
symbol
Name
Display
level
Setting range
Initial
value
SDP
PVinputscale
decimal point
position
EASY
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends
on the
input type
SH
Maximum
value
ofPV
input scale
EASY
-19999to30000,(SL<SH),|SH-SL|≤
30000
Depends
on the
input type
SL
Minimum value
ofPVinput
scale
EASY
Depends
on the
input type
BSL
PVinput
burnout action
STD
OFF: Disable
UP: Upscale
DOWN: Downscale
Depends
on the
input type
RJC
PVinput
reference
junction
compensation
PRO
OFF: RJC OFF
ON: RJC ON
ON
ERJC
PVinput
external RJC
setpoint
PRO -10.0
to60.0
(°C) 0.0
A.BS
PVanalog
input bias
STD
-100.0to100.0%
ofPVinputrangespan
(EUS)
0.0%of
PVinput
range
span
A.FL
PVanalog
inputlter
STD OFF, 1 to 120 s OFF
A.SR
PV
analog
input square
root extraction
PRO
OFF: No square root extraction.
1: Compute the square root. (The slope
equals “1.”)
2: Compute the square root. (The slope
equals “0.”)
OFF
A.LC
PVanalog
input low signal
cutoff
PRO 0.0
to5.0% 1.0%
18.2ListofParameters