18-18
IM 05P01C31-01EN
PVInputSettingMenu(Menu:PV)(Continuedfrompreviouspage)
Parameter
symbol
Name
Display
level
Setting range
Initial
value
SDP
PVinputscale
decimal point
position
EASY
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends
on the
input type
SH
Maximum
value
ofPV
input scale
EASY
-19999to30000,(SL<SH),|SH-SL|≤
30000
Depends
on the
input type
SL
Minimum value
ofPVinput
scale
EASY
Depends
on the
input type
BSL
PVinput
burnout action
STD
OFF: Disable
UP: Upscale
DOWN: Downscale
Depends
on the
input type
RJC
PVinput
reference
junction
compensation
PRO
OFF: RJC OFF
ON: RJC ON
ON
ERJC
PVinput
external RJC
setpoint
PRO -10.0
to60.0
(°C) 0.0
A.BS
PVanalog
input bias
STD
-100.0to100.0%
ofPVinputrangespan
(EUS)
0.0%of
PVinput
range
span
A.FL
PVanalog
inputlter
STD OFF, 1 to 120 s OFF
A.SR
PV
analog
input square
root extraction
PRO
OFF: No square root extraction.
1: Compute the square root. (The slope
equals “1.”)
2: Compute the square root. (The slope
equals “0.”)
OFF
A.LC
PVanalog
input low signal
cutoff
PRO 0.0
to5.0% 1.0%
18.2ListofParameters