336 Mains chokes
Selecting the mains choke
Degree of protection
IP20
Dimensions and weights
See dimension drawings of Mains chokes – CHK-0x on page 353.
For dimensions, wire sizes and tightening torques, see Mains chokes – CHK-0x on
page 353.
Installation guidelines
If an EMC filter is also installed, the mains choke is connected between the supply
and the EMC filter. See the diagram below.
For optimal operation of the choke, the drive and the choke must be mounted on
the same conductive surface.
Make sure the choke does not block the airflow through the drive module, and
that the air rising from the choke is deflected away from the air inlet of the drive
module
Keep the cable between the drive and the choke as short as possible.
WARNING! The surface of the mains choke becomes hot when in use.
Drive type
ACL30-04...
Frame Type Inductance
µH
-06A0 B CHK-02 4610
-09A0 B CHK-03 2700
-013A
-017A B CHK-04 1475
-023A C CHK-05/Internal 1130
-030A
-050A D CHK-07/Internal 450
-070A CHK-08/Internal 355