346 Resistor braking
Braking circuit commissioning
1. Enable the brake chopper function from parameter group 48 Brake chopper.
Note: Make sure the brake resistor is connected.
2. Adjust any other relevant parameters in the group 48 Brake chopper.
WARNING! If the drive is equipped with a brake chopper but the chopper is
not enabled by parameter setting, the internal thermal protection of the drive
against resistor overheating is not in use. In this case, the brake resistor
must be disconnected.