214 Parameters
Parameter groups 10…99
No. Bit/Name/Value/
Range
Description Def/Type
FbEq
(16b/32b)
10
10 START/STOP
Start/stop/direction, slowdown and end limits source
selections.
10.01 START FUNC
Selects the source for the start and stop control in
external control.
Note: This parameter cannot be changed while the
drive is running.
IN1 F IN2R/
enum
Not sel No source selected. 0
In1 Source of the start and stop commands is selected
by parameter 10.02 UP COMMAND. The start/stop is
controlled as follows:
1
3-wire Source of the start and stop commands is selected
by parameters 10.02 UP COMMAND and 10.03
DOWN COMMAND. The start/stop is controlled as
follows:
2
FBA Start and stop control from the source selected by
parameter 72.04 FB CW USED.
3
IN1 F IN2R The source selected by 10.02 UP COMMAND is the
forward start signal, the source selected by 10.03
DOWN COMMAND is the reverse start signal.
4
IN1S IN2DIR The source selected by 10.02 UP COMMAND is the
start signal (0 = stop, 1 = start), the source selected
by 10.03 DOWN COMMAND is the direction signal
(0 = forward, 1 = reverse).
5
Par. 10.02 Command
0
-
> 1 Start
1
-
> 0 Stop
Par. 10.02 Par. 10.03 Command
0
-
> 1 1 Start
Any 1
-
> 0 Stop
Any 0 Stop
Par. 10.02 Par. 10.03 Command
00Stop
10Start
forward
01Start
reverse
11Stop