EasyManuals Logo

ABB ACL30 User Manual

ABB ACL30
360 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #215 background imageLoading...
Page #215 background image
Parameters 215
PANEL Start and stop control from the panel. 6
EFB Start and stop control from parameter 02.15 EFB
MAIN CW.
7
10.02 UP COMMAND
Drive start up command.
This parameter is read-only.
DI1/
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
- / 1 = 1
10.03 DOWN COMMAND
Drive start down command.
This parameter is read-only.
DI 2/
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
- / 1 = 1
10.04 DRIVE ENABLE
Selects the source for the Drive enable signal.
1 = Run enable.
When this signal is switched Off, the drive does not
start, or if the drive was running, it will stop.
Note: This parameter cannot be changed while the
drive is running.
C.True/
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
- / 1 =1
10.05 EM STOP OFF1
Selects the source for the emergency stop OFF1.
0 = OFF1 active: The drive is stopped with the active
deceleration time. See section Emergency stop on
page 169.
Note: This parameter cannot be changed while the
drive is running.
True/
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
- / 1 =1
10.06 START DELAY
Defines the delay time to start modulation.
The contactor between drive and motor is closed at
this time. The signal 03.07 MOT CONTACT CTRL
can be used to control the motor contactor.
100 ms/
Real
0...1000 ms Delay time 1 = 1 ms
No. Bit/Name/Value/
Range
Description Def/Type
FbEq
(16b/32b)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACL30 and is the answer not in the manual?

ABB ACL30 Specifications

General IconGeneral
BrandABB
ModelACL30
CategoryDC Drives
LanguageEnglish

Related product manuals