16 pulse counter value function blocks PCGGIO:1 to PCGGIO:16 and 24 mA input
service values function blocks SMMI1_In1 to 6 – SMMI4_In1 to 6 are available in the
670 series IEDs.
The first LON address in every event function block is found in table
624
Table 624: LON adresses for Event functions
Function block First LON address in
function block
EVENT:1 1024
EVENT:2 1040
EVENT:3 1056
EVENT:4 1072
EVENT:5 1088
EVENT:6 1104
EVENT:7 1120
EVENT:8 1136
EVENT:9 1152
EVENT:10 1168
EVENT:11 1184
EVENT:12 1200
EVENT:13 1216
EVENT:14 1232
EVENT:15 1248
EVENT:16 1264
EVENT:17 1280
EVENT:18 1296
EVENT:19 1312
EVENT:20 1328
Event masks
The event mask for each input can be set individually from Parameter Setting Tool
(PST) under: Settings/ General Settings/ Monitoring / EventFunction as follows:
No events
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, event system itself make the reporting decision, (reporting criteria for
integers has no semantic, prefer to be set by the user)
1MRK505222-UUS C Section 17
Station communication
1009
Technical reference manual