The SPA addresses for the pulse counter values PCGGIO:1 to PCGGIO:16 are found
in table 630.
Table 630: SPA addresses for the PCGGIO function
Function block SPA address CNT_VAL SPA address NEW_VAL
PCGGIO:1 3-O-5834 3-O-5833
PCGGIO:2 3-O-5840 3-O-5839
PCGGIO:3 3-O-5846 3-O-5845
PCGGIO:4 3-O-5852 3-O-5851
PCGGIO:5 3-O-5858 3-O-5857
PCGGIO:6 3-O-5864 3-O-5863
PCGGIO:7 3-O-5870 3-O-5869
PCGGIO:8 3-O-5876 3-O-5875
PCGGIO:9 3-O-5882 3-O-5881
PCGGIO:10 3-O-5888 3-O-5887
PCGGIO:11 3-O-5894 3-O-5893
PCGGIO:12 3-O-5900 3-O-5899
PCGGIO:13 3-O-5906 3-O-5905
PCGGIO:14 3-O-5912 3-O-5911
PCGGIO:15 3-O-5918 3-O-5917
PCGGIO:16 3-O-5924 3-O-5923
I/O modules
To read binary inputs, the SPA-addresses for the outputs of the I/O-module function
block are used, that is, the addresses for BI1 – BI16. For SPA addresses, refer to
section
"Related documents".
Single command, 16 signals
The IEDs can be provided with a function to receive signals either from a substation
automation system or from the local HMI. That receiving function block has 16
outputs that can be used, for example, to control high voltage apparatuses in
switchyards. For local control functions, the local HMI can also be used.
Single command, 16 signals function consists of three function blocks; SINGLECMD:
1 to SINGLECMD:3 for 16 binary output signals each.
The signals can be individually controlled from the operator station, remote-control
gateway, or from the local HMI on the IED. For Single command, 16 signals function
block, SINGLECMD:1 to SINGLECMD:3, the address is for the first output. The other
Section 17 1MRK505222-UUS C
Station communication
1030