Name Values (Range) Unit Step Default Description
HarmRestrain2 Disabled
Enabled
- - Enabled Enable block of step 2 from harmonic restrain
tPCrv2 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 2
tACrv2 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 2
tBCrv2 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 2
tCCrv2 0.1 - 10.0 - 0.1 1.0 Parameter C for customer programmable
curve for step 2
tPRCrv2 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer programmable
curve for step 2
tTRCrv2 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer programmable
curve for step 2
tCRCrv2 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer programmable
curve for step 2
DirModeSel3 Disabled
Non-directional
Forward
Reverse
- - Non-directional Directional mode of step 3 (Disabled, Nondir,
Forward, Reverse)
Characterist3 ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
- - ANSI Def. Time Time delay curve type for step 3
Pickup3 1 - 2500 %IB 1 33 Residual current pickup for step 3 in % of IBase
t3 0.000 - 60.000 s 0.001 0.800 Independent time delay of step 3
TD3 0.05 - 999.00 - 0.01 0.05 Time multiplier for the dependent time delay
for step 3
IMin3 1.00 - 10000.00 %IB 1.00 33 Minimum current for step 3
t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves for
step 3
MultPU3 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current setting value
for step 3
Table continues on next page