Name Values (Range) Unit Step Default Description
ResetTypeCrv3 Instantaneous
IEC Reset
ANSI reset
- - Instantaneous Reset curve type for step 3
tReset3 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 3
HarmRestrain3 Disabled
Enabled
- - Enabled Enable block of step 3 from harmonic restrain
tPCrv3 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 3
tACrv3 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 3
tBCrv3 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 3
tCCrv3 0.1 - 10.0 - 0.1 1.0 Parameter C for customer programmable
curve step 3
tPRCrv3 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer programmable
curve step 3
tTRCrv3 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer programmable
curve step 3
tCRCrv3 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer programmable
curve for step 3
DirModeSel4 Disabled
Non-directional
Forward
Reverse
- - Non-directional Directional mode of step 4 (Disabled, Nondir,
Forward, Reverse)
Characterist4 ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
- - ANSI Def. Time Time delay curve type for step 4
Pickup4 1 - 2500 %IB 1 17 Residual current pickup for step 4 in % of IBase
t4 0.000 - 60.000 s 0.001 1.200 Independent (definitive) time delay of step 4
TD4 0.05 - 999.00 - 0.01 0.05 Time multiplier for the dependent time delay
for step 4
IMin4 1.00 - 10000.00 %IB 1.00 17 Minimum current for step 4
t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time in inverse curves step 4
Table continues on next page
1MRK505222-UUS C Section 7
Current protection
419
Technical reference manual