Voltage
Time
HystAbs1
PICKUP
TRIP
PICKUP
Pickup1
PICKUP
TRIP
t
tIReset1
Time
Time
Integrator
t
Frozen Timer
Linearly decreased
Instantaneous
Measured Voltage
tIReset1
ANSI05000020-2-en.vsd
ANSI05000020 V2 EN
Figure 259: Voltage profile causing a reset of the PICKUP signal for step 1, and inverse time delay
Definite time delay
When definite time delay is selected the function will operate as shown in figure 260.
Detailed information about individual stage reset/operation behavior is shown in figure
252 and figure 253 receptively. Note that by setting tResetn = 0.0s instantaneous reset
of the definite time delayed stage is ensured
Section 8 1MRK505222-UUS C
Voltage protection
510
Technical reference manual