1 10
1
10
100
1000
2 403 4 5 20 30
TD = 2
TD = 3
TD = 4
TD = 5
TD = 6
TD = 7
TD = 8
TD = 9
TD = 10
TD = 1
OVEREXCITATION IN %
Time (s)
IEEE OVEREXCITATION CURVES
en01000373_ansi.vsd
(M-Emaxcont)*100)
TD = 60
TD = 20
ANSI01000373 V1 EN
Figure 273: Delays inversely proportional to the square of the overexcitation
The critical value of excitation M is determined indirectly via OEXPVPH (24) setting
Pickup2. Pickup2 can be thought of as a no-load voltage at rated frequency, where the
inverse law should be replaced by a short definite delay, t_MinTripDelay. If, for
example, Pickup2 = 140 %, then M is according to equation
144.
( )
Pickup2 f
M 1.40
Vn/fn
= =
ANSIEQUATION2286 V1 EN (Equation 144)
The Tailor-Made law allows a user to design an arbitrary delay characteristic. In this
case the interval between M = Pickup1, and M = Mmax is automatically divided into
Section 8 1MRK505222-UUS C