V=-3V0
Ipickup
Operate region
I=3Io
mta line
RCADir
ROADir
en05000252_anis.vsd
IEC05000252-ANIS V1 EN
Figure 288: I & V directional operating principle for CVGAPC function
where:
RCADir
is -75°
ROADir
is 50°
The second principle, referred to as "IcosPhi&V" in the parameter setting tool, checks
that:
that the product I·cos(Φ) is bigger than the set pick-up level, where Φ is angle
between the current phasor and the mta line
that the phasor of the measured current is within the operating region (defined by
the I·cos(Φ) straight line and the relay operate angle, ROADir parameter setting;
see figure
288).
1MRK505222-UUS C Section 10
Multipurpose protection
573
Technical reference manual