If the pulse is set to be adaptive, it is not possible for the pulse to exceed tOpenPulse or
tClosePulse.
The execute output pulses are reset when:
the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
the timer tOpenPulse or tClosePulse has elapsed
an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.
There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in closed
position and a close command is executed. In these cases, with the additional condition
that the configuration parameter AdaptivePulse is true, the execute output pulse is
always activated and resets when tStartMove has elapsed. If the configuration
parameter AdaptivePulse is set to false the execution output remains active until the
pulse duration timer has elapsed.
If the start position indicates bad state (OPENPOS=1 and CLOSEPOS
=1) when a command is executed the execute output pulse resets only
when timer tOpenPulse or tClosePulse has elapsed.
An example of when a primary device is open and an open command is executed is
shown in figure 340 .
EXE_OP
CLOSEPOS
EXE_OP
OPENPOS
AdaptivePulse=FALSE
tOpenPulse
tOpenPulse
AdaptivePulse=TRUE
tStartMove timer
en05000099.vsd
IEC05000099 V1 EN
Figure 340: Open command with open position indication
1MRK505222-UUS C Section 12
Control
673
Technical reference manual