Name Values (Range) Unit Step Default Description
FrLowLim 0.000 - 100.000 Hz 0.001 47.000 Low limit (physical value)
FrLowLowLim 0.000 - 100.000 Hz 0.001 45.000 Low Low limit (physical value)
FrLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common for
all limits)
VGenZeroDb 1 - 100 %VB 1 5 Zero point clamping in % of VBase
IGenZeroDb 1 - 100 %IB 1 5 Zero point clamping in % of IBase
VMagComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 5% of
Vn
VMagComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 30%
of Vn
VMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 100%
of Vn
IMagComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 5% of
In
IMagComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 30%
of In
IMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 100%
of In
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of In
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of In
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of In
Table 554: CMMXU Non group settings (basic)
Name
Values (Range) Unit Step Default Description
IA_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Operation Disabled
Enabled
- - Disabled Disbled/Enabled operation
IBase 1 - 99999 A 1 3000 Base setting for current level in A
IA_Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
IA_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IA_AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IB_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IB_Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
Table continues on next page
Section 15 1MRK505222-UUS C
Monitoring
916
Technical reference manual