Name Values (Range) Unit Step Default Description
IB_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IB_AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IC_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IC_Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
IC_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IC_AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Table 555: CMMXU Non group settings (advanced)
Name Values (Range) Unit Step Default Description
IA_ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
IA_HiHiLim 0.000 -
10000000000.000
A 0.001 900.000 High High limit (physical value)
IA_HiLim 0.000 -
10000000000.000
A 0.001 800.000 High limit (physical value)
IMagComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 5% of
In
IMagComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 30%
of In
IA_LowLim 0.000 -
10000000000.000
A 0.001 0.000 Low limit (physical value)
IA_LowLowLim 0.000 -
10000000000.000
A 0.001 0.000 Low Low limit (physical value)
IMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 100%
of In
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of In
IA_Min 0.000 -
10000000000.000
A 0.001 0.000 Minimum value
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of In
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of In
IA_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
IB_ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
IB_HiHiLim 0.000 -
10000000000.000
A 0.001 900.000 High High limit (physical value)
Table continues on next page
1MRK505222-UUS C Section 15
Monitoring
917