Name Values (Range) Unit Step Default Description
IB_HiLim 0.000 -
10000000000.000
A 0.001 800.000 High limit (physical value)
IB_LowLim 0.000 -
10000000000.000
A 0.001 0.000 Low limit (physical value)
IB_LowLowLim 0.000 -
10000000000.000
A 0.001 0.000 Low Low limit (physical value)
IB_Min 0.000 -
10000000000.000
A 0.001 0.000 Minimum value
IB_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
IC_ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
IC_HiHiLim 0.000 -
10000000000.000
A 0.001 900.000 High High limit (physical value)
IC_HiLim 0.000 -
10000000000.000
A 0.001 800.000 High limit (physical value)
IC_LowLim 0.000 -
10000000000.000
A 0.001 0.000 Low limit (physical value)
IC_LowLowLim 0.000 -
10000000000.000
A 0.001 0.000 Low Low limit (physical value)
IC_Min 0.000 -
10000000000.000
A 0.001 0.000 Minimum value
IC_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
Table 556: VNMMXU Non group settings (basic)
Name
Values (Range) Unit Step Default Description
VA_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Operation Disabled
Enabled
- - Disabled Disbled/Enabled operation
VBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level in kV
VA_Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
VA_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VA_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
VA_AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VB_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Table continues on next page
Section 15 1MRK505222-UUS C
Monitoring
918
Technical reference manual