Name Values (Range) Unit Step Default Description
VCA_Max 0.000 -
10000000000.000
V 0.001 500000.000 Maximum value
VCA_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VCA_AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Table 559: VMMXU Non group settings (advanced)
Name Values (Range) Unit Step Default Description
VAB_ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
VAB_HiHiLim 0.000 -
10000000000.000
V 0.001 450000.000 High High limit (physical value)
VAB_HiLim 0.000 -
10000000000.000
V 0.001 420000.000 High limit (physical value)
VAB_LowLim 0.000 -
10000000000.000
V 0.001 380000.000 Low limit (physical value)
VAB_LowLowLim 0.000 -
10000000000.000
V 0.001 350000.000 Low Low limit (physical value)
VMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 100%
of Vn
VAB_Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
VAB_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
VBC_ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
VBC_HiHiLim 0.000 -
10000000000.000
V 0.001 450000.000 High High limit (physical value)
VBC_HiLim 0.000 -
10000000000.000
V 0.001 420000.000 High limit (physical value)
VBC_LowLim 0.000 -
10000000000.000
V 0.001 380000.000 Low limit (physical value)
VBC_LowLowLim 0.000 -
10000000000.000
V 0.001 350000.000 Low Low limit (physical value)
VBC_Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
VBC_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
VCA_ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
VCA_HiHiLim 0.000 -
10000000000.000
V 0.001 450000.000 High High limit (physical value)
VCA_HiLim 0.000 -
10000000000.000
V 0.001 420000.000 High limit (physical value)
Table continues on next page
1MRK505222-UUS C Section 15
Monitoring
921
Technical reference manual