Name Values (Range) Unit Step Default Description
VCA_LowLim 0.000 -
10000000000.000
V 0.001 380000.000 Low limit (physical value)
VCA_LowLowLim 0.000 -
10000000000.000
V 0.001 350000.000 Low Low limit (physical value)
VCA_Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
VCA_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
Table 560: CMSQI Non group settings (basic)
Name Values (Range) Unit Step Default Description
3I0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
3I0Min 0.000 -
10000000000.000
A 0.001 0.000 Minimum value
3I0Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
3I0RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
3I0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
3I0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Operation Disabled
Enabled
- - Disabled Disbled/Enabled operation
3I0AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
3I0AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
3I0AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
I1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
I1Min 0.000 -
10000000000.000
A 0.001 0.000 Minimum value
I1Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
I1RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
I1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
I1AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
Table continues on next page