Name Values (Range) Unit Step Default Description
I1AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
I2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
I2Min 0.000 -
10000000000.000
A 0.001 0.000 Minimum value
I2Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
I2RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
I2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
I2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
I2AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
I2AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
Table 561: CMSQI Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
3I0ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
3I0HiHiLim 0.000 -
10000000000.000
A 0.001 900.000 High High limit (physical value)
3I0HiLim 0.000 -
10000000000.000
A 0.001 800.000 High limit (physical value)
3I0LowLim 0.000 -
10000000000.000
A 0.001 0.000 Low limit (physical value)
3I0LowLowLim 0.000 -
10000000000.000
A 0.001 0.000 Low Low limit (physical value)
3I0AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
I1ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
I1HiHiLim 0.000 -
10000000000.000
A 0.001 900.000 High High limit (physical value)
I1HiLim 0.000 -
10000000000.000
A 0.001 800.000 High limit (physical value)
I1LowLim 0.000 -
10000000000.000
A 0.001 0.000 Low limit (physical value)
I1LowLowLim 0.000 -
10000000000.000
A 0.001 0.000 Low Low limit (physical value)
Table continues on next page
1MRK505222-UUS C Section 15
Monitoring
923
Technical reference manual