4 Fuel Output Modes and Changeover Options
Mk8 MM Manual Page | 119
4.7 Limitations of DFOM and COF
The following functions cannot be used if the MM is configured for Dual Fuel Output Mode or COF:
Fully Metered Combustion.
Single Valve Pilot (Option 130 settings 3, 4 &5).
No Pilot Mode (Direct Spark, option 111 setting 2) on Gas fuels only.
Multi-burner mode will operate with Dual Fuel Output Mode but is not possible with COF.
Although it is possible to configure 2 liquid fuels, it is not possible to have pressure sensors for both
fuels at the same time.
Piggyback valve arrangement, separate servomotor is required for each fuel.
Dual Fuel Output Mode and COF features will not be displayed on the Mk7 DTI, only Mk8 DTI is able
to display these features.