18 Operation
Mk8 MM Manual Page | 347
18.17 First Outs
Figure 18.17.i First Outs
Press (if enabled) in the Home Screen in Figure 18.1.i to view the First Outs screen. The functions
of a first out when active is summarised below:
Function When Active
Description
Disabled
Does not function.
Monitor
Burner continues firing, but the events will be logged.
Non-recycle
Burner stops firing and the first out must be reset for the burner to restart.
Recycle
Burner stops firing and restarts automatically when the input state changes.
Stop EGA Sampling
Burner continues firing, but the EGA stops sampling.
Stops EGA Trimming
Burner continues firing, but the EGA trim stops operating.