10 Water Level Control
Mk8 MM Manual Page | 191
10.9.5 Setting 1
st
Low Level
Figure 10.9.5.i Commission 1
st
Low Level
After storing or updating the 2
nd
low level, press to increase the water level to the 1
st
low level.
Once the water has risen to the required 1
st
low level, turn the pump off and close the valve. Let the readings
settle and press .
If required, the 1
st
low level can be updated by adjusting the water level and pressing once the
position has been stored.