18 Operation
Mk8 MM Manual Page | 338
18.12 Water Level Screen
18.12.1 Water Level – Status
Figure 18.12.1.i Water Level
Press on the water level probes or the feed water pump (if enabled) in the Home screen in Figure 18.1.i to
view the Water Level Status screen, which shows the following information:
• Capacitance probe, external level sensor readings
• Auxiliary alarm inputs and 2
nd
low probe water detection
• Combined water level reading
• Feed water pump state on/off, VSD output, servomotor position
• Feed water pump bypass on/off, pump on/off levels
• Feed water temperature
• Commissioned 2
nd
low, 1
st
low, pre 1
st
low, control point, pre high and high water levels
Press to continuously cycle the alarm outputs every 2 seconds without shutting the burner down.
Press to check the water level alarms. There is time delay for the burner to reach 1
st
low
(expansion option 22), allowing the operator to decrease the water level to check the 1
st
low alarm. If the
water does not drop to 1
st
low within this time, the shunt switch test is cancelled, and the MM reverts to
normal operation. There is additional delay (expansion option 23) to allow the operator to decrease the water
to 2
nd
low to check the 2
nd
low alarm. If the water level does not drop in this time, the MM leaves shunt switch
test and the burner will turn off. The timer will display when doing these tests. After reaching 2
nd
low, if the
water level does not rise to control point within 10 minutes, alarms will occur.

Table of Contents

Other manuals for AUTOFLAME Mk8 MM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUTOFLAME Mk8 MM and is the answer not in the manual?

AUTOFLAME Mk8 MM Specifications

General IconGeneral
BrandAUTOFLAME
ModelMk8 MM
CategoryController
LanguageEnglish

Related product manuals