10 Water Level Control
Mk8 MM Manual Page | 197
10.9.10 Adjust Control Point
Figure 10.9.10.i Adjust Control Point
The control point which set during water level commissioning can be adjusted through Online Changes.
Press in Online Changes and go to the Water Level Status and change the control point as
required. This cannot be set higher than the high water level or lower than 1
st
low level. The pump on/off
percentages and pre-level alarms will change with the new control point.
Once the control point has been adjusted, press to save, and then press to leave the
Water Level Status screen.