EasyManua.ls Logo

AUTOFLAME Mk8 MM - Servomotors with Autoflame Valves

AUTOFLAME Mk8 MM
395 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Commissioning Procedure
Mk8 MM Manual Page | 71
3.3.4 Servomotors with Autoflame Valves
On threaded valves, the pin on the top of the valve is 90 degrees opposite from the position of the butterfly
valve.
On flanged valves, the pin on the top of the valve is in line with the position of the butterfly valve.
For both valves the external visual position indicator is in line with the position of the butterfly valve.
Regardless of the type of valve being used, the servomotor is dispatched from the factory with the
potentiometer in the zero position. The same servomotor will be correct for both types of valve, as the
servomotor for the threaded valve is mounted at 90 degrees different from the flanged valve.
Figure 3.3.4.i Valve Pin Positions

Table of Contents

Other manuals for AUTOFLAME Mk8 MM

Related product manuals