Page #168 background image
10 Water Level Control
Mk8 MM Manual Page | 168
10.4 Ways of Level Sensing
10.4.1 Overview
Water level control requires a minimum of two water level sensing devices, one of which must be an
analogue device (capacitance probe or external level sensing device).
The MM will show the capacitance probe reading(s), the external level sensor reading, and a combined
reading of the optioned analogue sensing devices, as well as the 2
nd
low probe and auxiliary alarm inputs
status.
Figure 10.4.1.i Water Level Status – Combined Level Sensing