19 Errors & Lockouts
Mk8 MM Manual Page | 393
19.5 Forced Commission Reasons
In addition to when there is a setting conflict, the MM will be forced into commission mode if any of the forced
commission reason occurs.
Forced Commission Message
• Selected fuel must be commissioned.
Servo configuration does not match commissioning.
• Option 8 and/or expansion option 80 do not match the last commission settings.
VSD configuration does not match commissioning.
•
VSD settings for channels 5 and 6 must be the same as the last commission settings.
Golden start optioned but not commissioned.
• Commission golden start position (see section 3.4.8).
FGR optioned but not commissioned.
•
Commission FGR start position (see section 3.4.9).
Trim channel does not match commissioning.
• Option 76 trim channel must be the same as the last commission settings.
Fuel/air-rich trim ranges changed.
• Parameter 13 and/or parameter 19 do not match last commission settings.
BC Option/parameter mismatch.
• BC options 110 – 160 must be set the same as their corresponding parameters.
• An option value is outside the allowed range.
• A parameter value is outside the allowed range.
Invalid expansion option value.
•
An expansion option value is outside the allowed range.
• Option settings have been reset due to data lost in an EEPROM error.
Parameters have been reset.
• Parameter settings have been reset due to data lost in an EEPROM error.
Expansion options have been reset.
• Expansion option settings have been reset due to data lost in an EEPROM error.
VPS sensor not commissioned.
• Gas pressure sensor has been enabled but not commissioned.
Commissioned gas pressure during valve proving too low.
• Gas pressure stored during valve proving is less than option/parameters 133 and/or 136.
Commissioned running gas pressure too low.
•
Gas pressure at one or more commissioned points is less than option/parameter 136.
APS sensor not commissioned.
• Air pressure has been enabled but not commissioned.
Commissioned air pressure too low.
• Air pressure at one or more commissioned points is less than option/parameters 147 and/or 149.
IR Upload was completed successfully, check configuration then restart.
• Check data has uploaded successfully before restarting in run mode.