10 Water Level Control
Mk8 MM Manual Page | 190
10.9.4 Setting 2
nd
Low Level
Figure 10.8.4.i Commission 2
nd
Low Level
After storing or updating the end of probe level, press to increase the water level to the 2
nd
low
level. It is recommended that there is a 25mm (1”) gap between the commissioned levels, which is
approximately 500Hz.
Once the water has risen to the required 2
nd
low level, turn the pump off and close the valve. Let the
readings settle and press .
If required, the 2
nd
low level can be updated by adjusting the water level and pressing once the
position has been stored.