EasyManua.ls Logo

AUTOFLAME Mk8 MM - Continuous Pilot with Interrupted Pilot Sequence

AUTOFLAME Mk8 MM
395 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 MM Features
Mk8 MM Manual Page | 130
6.4.1 Continuous Pilot with Interrupted Pilot Sequence
Start
T53 Circuit
Made?
No
Yes
Purge
Ignition On
Main Valves On
Stat Circuit
Made?
Ignition Off
Pilot Valves On
Stat Circuit
Made?
Firing
Stat Circuit
Made?
Move to low fire
Continuous Pilot
T53 Circuit
Made?
Post purge
Continuous
Pilot timer
expired?
Main Valves Off
T53 Circuit
Made?
Yes
No
Yes
No
Yes
Pilot Valves Off
No
Yes
No
No
Yes
Yes
No
Return to Start
Continuous
Pilot offset
breached?
Yes
No
Move to Golden start
(if commissioned)
Main Valves Off
Pilot Valves Off
Pilot Valves On

Table of Contents

Other manuals for AUTOFLAME Mk8 MM

Related product manuals