2 Options & Parameters
Mk8 MM Manual Page | 57
2.2 Parameters
Figure 2.2.i Commission Mode – Parameters
Press in the Commission Mode screen to access the Parameters. Any number of options/
parameters can be changed at one time. By pressing MM, PID, EGA, DTI or BC at the bottom of the screen,
the options/ parameters can be grouped together by feature.
When the changes have been made to suit the application’s needs, press Exit to go back to the Commission
Mode screen.
Options/ parameters 110 – 160 are the burner control settings and are safety critical; these must be entered
the same for both the option and parameter value. If these BC options and parameters do not match, there
will be an option/parameter conflict.
To set all the options, parameters and expansion options to the default values and erase the commissioning
data, set option/ parameter 160 to 5. The MM will then automatically restart and go into Commission mode.