2 Options & Parameters
Mk8 MM Manual Page | 58
Par.# Default Range Description
DTI: Sequence Scan Time Set When Units Goes Offline
If a sequenced MM drops out of the sequence loop, there is a time delay
before the next scan time.
DTI: Number of Boilers Initially On
This sets the number of boilers which when powered on after a shutdown,
are in the On state in the sequence loop. This set should be set to the
highest MM ID number (see parameter 57) if the application requires all
the MMs to be On in the sequence loop when powered back on.
EGA: Delay Before EGA Commission Can be Stored
During commission and single point change, there is a delay before the
EGA values are stored. This value should be set in proportion to how long
it takes for the gases to reach the EGA
If a sequenced MM does not start modulating after being asked to by the
lead MM, it is ignored in the sequencing loop. Upon the next scan time, if
the MM modulates as required, it will be included in the sequencing loop.
EGA: Trim Delay After Drain
This is the delay after draining the sample, before the trim cycle start.
Within this delay, the trim correction on the air damper or VSD is
maintained while the EGA drains and the cells are purged with air.
Mk7 - For use with Mk7 EGA
Mk8 Protocol (Legacy) – For use with Mk8 EGA
Mk8 Protocol (RS485) – For use with Mk8 EGA EVO
EGA: CO Used for Trim on Oil
If the fuel has been set as oil (see options/ parameters 150 to 153), then
the trim function can include CO to calculate the required trim correction.
EGA: Commission Fuel-Rich Trim
The % of air damper movement when commissioning fuel-rich trim.
EGA: Trim Reset Angular Rate
This is the change time in the fuel valve angle per minute that will reset the
trim correction.
0.0 – 90.0 degrees per minute