10 Water Level Control
Mk8 MM Manual Page | 169
10.4.2 Configuration
The following tables show the expansion options which need to be set on the Mk8 MM for the different ways
of water level detection.
Expansion Option
Description
Setting
1. One capacitance probe, external level sensor
1
Water level control function
1
3
Capacitance probes
1
4
External level sensor
1
27
Probe mismatch threshold
As required
28
Capacitance probe still water threshold
As required
29
Capacitance probe filter time
As required
30
External level sensor scaling
As required
31
External level sensor filter time
As required
2. One capacitance probe, external level sensor, auxiliary alarm inputs
1
Water level control function
1
3
Capacitance probes
1
4
External level sensor
1
5
Auxiliary alarm inputs
1
27
Probe mismatch threshold
As required
28
Capacitance probe still water threshold
As required
29
Capacitance probe filter time
As required
30
External level sensor scaling
As required
31
External level sensor filter time
As required
3. One capacitance probe, external level sensor, 2
nd
low probe
1
Water level control function
1
3
Capacitance probes
1
4
External level sensor
1
6
Second low probe
1
27
Probe mismatch threshold
As required
28
Capacitance probe still water threshold
As required
29
Capacitance probe filter time
As required
30
External level sensor scaling
As required
31
External level sensor filter time
As required
4. One capacitance probe, external level sensor, 2
nd
low probe, auxiliary alarm inputs
1
Water level control function
1
3
Capacitance probes
1
4
External level sensor
1
5
Auxiliary alarm inputs
1
6
Second low probe
1
27
Probe mismatch threshold
As required
28
Capacitance probe still water threshold
As required
29
Capacitance probe filter time
As required
30
External level sensor scaling
As required
31
External level sensor filter time
As required
5. One capacitance probe, 2
nd
low probe
1
Water level control function
1
3
Capacitance probes
1
6
Second low probe
1
27
Probe mismatch threshold
As required
28
Capacitance probe still water threshold
As required
29
Capacitance probe filter time
As required

Table of Contents

Other manuals for AUTOFLAME Mk8 MM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUTOFLAME Mk8 MM and is the answer not in the manual?

AUTOFLAME Mk8 MM Specifications

General IconGeneral
BrandAUTOFLAME
ModelMk8 MM
CategoryController
LanguageEnglish

Related product manuals