6 MM Features
Mk8 MM Manual Page | 131
6.4.2 Continuous Pilot with Intermittent Pilot Sequence
Start
T53 Circuit
Made?
No
Yes
Purge
Ignition On
Main Valves On
Stat Circuit
Made?
Ignition Off
Pilot Valves On
Stat Circuit
Made?
Firing
Stat Circuit
Made?
Move to low fire
T53 Circuit
Made?
Post purge
Continuous
Pilot timer
expired?
Main Valves Off
T53 Circuit
Made?
Yes
No
Yes
No
Yes
Pilot Valves Off
No
Yes
No
No
Yes
Yes
No
Return to Start
Continuous
Pilot offset
breached?
Yes
No
Main Valves &
Pilot Valves Off
Continuous Pilot
Move to Golden start
(if commissioned)