14 Direct Modbus
Mk8 MM Manual Page | 263
# Type Description Details
Fully Metered Fuel Pressure
Metric: mbar x 10
Imperial: “WG x 10 or PSI x 100
Fully Metered Fuel Channel
Correction Fraction
Applied correction x 1000
Fully Metered Current Air Mass
Flow Thousands
Metric: kgs x 1000
Imperial: lbs x 1000
Fully Metered Current Air Mass
Flow Singles
Metric: 0 to 999 kgs
Imperial: 0 to 999 lbs
Fully Metered Commissioned
Air Mass Flow Thousands
Metric: kgs x 1000
Imperial: lbs x 1000
Fully Metered Commissioned
Air Mass Flow Singles
Metric: 0 to 999 kgs
Imperial: 0 to 999 lbs
Fully Metered Current Air
Volume Flow Thousands
Fully Metered Current Air
Volume Flow Singles
Fully Metered Air Flow Meter
Current (4-20mA) Signal
Fully Metered Air Temperature
Metric: °C x10
Imperial: °F x 10
Fully Metered Air Pressure
Metric: mbar x 10
Imperial: “WG x 10
Fully Metered Air Channel
Correction Fraction
Applied correction x 1000
Fully Metered Atmospheric Air
Pressure
Metric: mbar x 10
Imperial: “WG x 10
Metric: temperature °C, pressure Bar x 10, low pressure
Bar x 100
Imperial: temperature °F, pressure PSI, low pressure PSI
x 10
After 1 minute of no Modbus communications to the unit,
the MM will ignore this required value and use the
required setpoint set on the MM’s status screen.
Percentage (%)
40131 must be set to 1 to change the firing rate remotely
Remote Firing Rate Enable
0 = Remote firing rate disabled
1 = remote firing rate enabled