19 Errors & Lockouts
Mk8 MM Manual Page | 376
Lockout
Message
Description
16
Prolonged Lockout Reset
Prolonged voltage detected on terminal 56/ lockout reset
button permanently pressed
Check lockout reset button is not pressed
Check wiring on terminal 56
17
Gas Pressure Low
Gas pressure low limit exceeded while firing(gas sensor)
Check gas pressure
Check option/ parameter 136
18
Gas Pressure High
Gas pressure high limit exceeded while firing (gas sensor)
Check gas pressure
Check option/ parameter 137
19
RAM Test Failed
Hardware fault
Contact Autoflame approved local tech centre
20
PROM Test Failed
Hardware fault
Contact Autoflame approved local tech centre
21
FSR Test 1A
Internal relay test failed
Check wiring and voltages on terminals 50 63
22
FSR Test 2A
Internal relay test failed
Check wiring and voltages on terminals 50 63
23
FSR Test 1B
Internal relay test failed
Check wiring and voltages on terminals 50 63
24
FSR Test 2B
Internal relay test failed
Check wiring and voltages on terminals 50 63
25
Watchdog Fail 2A
Internal check failed
Contact Autoflame approved local tech centre
26
Watchdog Fail 2B
Internal check failed
Contact Autoflame approved local tech centre
27
Watchdog Fail 2C
Internal check failed
Contact Autoflame approved local tech centre
28
Watchdog Fail 2D
Internal check failed
Contact Autoflame
29
Input Fault
Power supply fault
Check mains voltage to the MM
32
Gas Pressure Low Limit
Gas pressure lower than commissioned VPS value
Check gas pressure sensor value
Check option/parameter 136
33
VPS Air Zeroing
Gas pressure sensor cannot be zeroed at VPS venting
Check gas pressure is within zero range (see Autoflame Sensors Guide)
Check vent valve
36
Oil Pressure Too Low
Oil pressure below offset lower limit during running
Check option/parameter 139
Check oil pressure sensor
37
Oil Pressure Too High
Oil pressure above offset upper limit during running
Check option/parameter 140
Check oil pressure sensor
39
Freeze Timeout
MM kept in Phase Hold for more than 10minutes
MM kept in Phase Hold during commissioning for more than 10 minutes
40
Purge Air Pressure Low
Insufficient air pressure during purge
Check option/parameter 141
Check air pressure sensor/ air pressure switch