2 Options & Parameters
Mk8 MM Manual Page | 60
Par.# Default Range Description
29
1000
MM: Load Sensor Adjustment
This adjusts the load sensor (voltage) reading, as a percentage of the
reading.
800 1200
Value 1000 = 100.0% of actual reading
30
10
MM: Load Sensor Filter Time
1 40
Seconds
31
0
EGA: (Mk7 Only) Efficiency Calculation Method
For the Mk8 EGA, efficiency calculation method is set on the EGA itself.
0
English
1
European
32
-
Unused
33
-
Unused
34
-
Unused
35
-
Unused
36
-
Unused
37
-
Unused
38
***
MM: Commissioning Password Code 1
0 255
Code 1
39
***
MM: Commissioning Password Code 2
0 255
Code 2
40
0
MM: Display Units
0
Metric units
1
Imperial units
41
0
MM: Gas Pressure Units
This will set the units displayed for the Autoflame gas pressure sensor
optioned. Note, PSI units are not available for sensor MM80006.
0
mbar
1
inWG
2
PSI
42
0
MM: Oil Pressure Units
This will set the units displayed for the Autoflame oil pressure sensor
optioned.
0
Bar
1
PSI
43
-
MM: Air Pressure Sensor Units
This will set the units displayed for the Autoflame air pressure sensor.
0
mbar
1
inWG
44
-
Unused
45
-
Unused
46
-
Unused

Table of Contents