EasyManuals Logo

AUTOFLAME Mk8 MM User Manual

AUTOFLAME Mk8 MM
395 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #60 background imageLoading...
Page #60 background image
2 Options & Parameters
Mk8 MM Manual Page | 60
Par.# Default Range Description
29
1000
MM: Load Sensor Adjustment
This adjusts the load sensor (voltage) reading, as a percentage of the
reading.
800 – 1200
Value 1000 = 100.0% of actual reading
30
10
MM: Load Sensor Filter Time
1 – 40
Seconds
31
0
EGA: (Mk7 Only) Efficiency Calculation Method
For the Mk8 EGA, efficiency calculation method is set on the EGA itself.
0
English
1
European
32
-
Unused
33
-
Unused
34
-
Unused
35
-
Unused
36
-
Unused
37
-
Unused
38
***
MM: Commissioning Password Code 1
0 – 255
Code 1
39
***
MM: Commissioning Password Code 2
0 – 255
Code 2
40
0
MM: Display Units
0
Metric units
1
Imperial units
41
0
MM: Gas Pressure Units
This will set the units displayed for the Autoflame gas pressure sensor
optioned. Note, PSI units are not available for sensor MM80006.
0
mbar
1
inWG
2
PSI
42
0
MM: Oil Pressure Units
This will set the units displayed for the Autoflame oil pressure sensor
optioned.
0
Bar
1
PSI
43
-
MM: Air Pressure Sensor Units
This will set the units displayed for the Autoflame air pressure sensor.
0
mbar
1
inWG
44
-
Unused
45
-
Unused
46
-
Unused

Table of Contents

Other manuals for AUTOFLAME Mk8 MM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUTOFLAME Mk8 MM and is the answer not in the manual?

AUTOFLAME Mk8 MM Specifications

General IconGeneral
BrandAUTOFLAME
ModelMk8 MM
CategoryController
LanguageEnglish

Related product manuals