EasyManuals Logo

AUTOFLAME Mk8 MM User Manual

AUTOFLAME Mk8 MM
395 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #95 background imageLoading...
Page #95 background image
3 Commissioning Procedure
Mk8 MM Manual Page | 95
How to use this information:
1. Measure Volumetric flow of gas for 1min in ft3 (i.e. ft3/min). Note 1m3 = 35.31ft3
2. Multiply this volume flow by 60 to give volumetric flow per hour (i.e. ft3/hr).
3. Measure the pressure of the gas supply.
4. Use the table above to obtain a conversion factor.
5. Multiply the volume flow per hour by the conversion factor to obtain a volume at reference conditions.
6. For natural gas, the calorific value is typically 1000 Btu/ft3. To obtain the firing rate of the boiler at
standard reference conditions multiply the volume at reference conditions by 1000.
Represented as an equation:
Firing rate = (Measured Volumetric flow per minute x 60 x Conversion factor x 1000) Btu/hr

Table of Contents

Other manuals for AUTOFLAME Mk8 MM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUTOFLAME Mk8 MM and is the answer not in the manual?

AUTOFLAME Mk8 MM Specifications

General IconGeneral
BrandAUTOFLAME
ModelMk8 MM
CategoryController
LanguageEnglish

Related product manuals