184 CONFIGURA TION
13.6.1.1 DIO X SETUP / DIO1/2/3/4 Output mode enable PINs 271 / 277 / 283 / 2 89
Note. The terminal logic level is sensed by the input function irrespective of the output mode selection.
13.6.1.2 DIO X SETUP / DIO1/2/3/4 OP val rectify enable PINs 272/ 2 78 / 284 /290
The digital output is generated by
comparing an internal linear or logic signal
with a threshold.
E.g. Linear speed feedback.
The rectified mode will enable the digital
output to change state at a chosen speed
for both directions of rotation.
The bipolar mode will enable the digital
output to change state at only one chosen
point in the entire range of positive or negative rotation.
13.6.1.3 DIO X SETUP / DIO 1/2/3/4 OP comp threshold PINs 273 / 279 / 285 / 290
The output of the comparator will be high w hen the signal from the rectifier mode box exceeds the threshold.
The comparator output is lo w for identical inputs. For comparing logic values alw ays put 0.00% in the
threshold windo w.
13.6.1.4 DIO X SETUP / DIO1/2/3/4 OP inversion PINs 274 / 280 / 286 / 29 1
DIO1 Di
g
ital IO
DIO1
High value
Low value
GO TO
DIO1
GET FRO M
PIN 272
Rect/Bipolar
PIN 271
OP mode en
PIN 275
PIN 276
T 1 8
PIN 274
PIN 273 Threshold
PIN
68 5
DIO Monitor
PIN 163
DIO1 (T 18) SETUP 4
271)DIO1 OP MO DE
271)DIO1 OP MO DE
DISABLED
PARA METER RANGE DEF AULT PIN
DIO1 OP M ODE ENABLED or DIS ABLED DIS ABLED 271
Enables the output mode of
operation of the DIOX terminal.
DIO1 (T 18) SETUP 4
272)DIO1 RECTIFY EN
272)DIO1 RECTIFY EN
DISABLED
PARA METER RA NGE DEFAULT PIN
DIO1 REC TIFY EN ENABLED or DISABLED DISABLED 272
Selects rectified or bipolar
mode for the OP generator.
DIO1 (T 18) SETUP 4
273)DIO1 THRESHOLD
273)DIO1 THRESHOLD
0.00%
PARA METER RA NGE DEFAULT PIN
DIO 1 THRESHOLD + /- 300.00% 0.00% 273
Sets the comparator threshold
for the DIO X OP generator.
DIO1 (T 18) SETUP 4
274)DIO1 IN VERT M ODE
274)DIO1 IN VERT M ODE
NON INVERT
PARA METER RAN GE DEFA ULT PIN
DIO1 INVERT MODE INVERT, NON INVERT N ON INVERT 274
Allo ws the comparator output
logic to be inverted for DIO X.

Table of Contents