Chapter 4 Parameters
4-59
460V series 0.1 to 510.0V Factory Setting: 440.0
01.28 Mid-Point Frequency (Fmid) (Motor 1) Unit: Hz
Settings 0.10 to 599.00Hz
Factory Setting: 1.50
01.29 Mid-Point Voltage (Vmid) (Motor 1) Unit: V
Settings 115V/230V series 0.1 to 255.0V Factory Setting: 10.0
460V series 0.1 to 510.0V Factory Setting: 20.0
01.30 Minimum Output Frequency (Fmin) (Motor 1) Unit: Hz
Settings 0.10 to 599.00Hz
Factory Setting: 1.50
01.31 Minimum Output Voltage (Vmin) (Motor 1) Unit: V
Settings 115V/230V series 0.1 to 255.0V Factory Setting: 10.0
460V series 0.1 to 510.0V Factory Setting: 20.0
01.32 Maximum Voltage Frequency (Fbase) (Motor 2) Unit: Hz
Settings 0.10 to 599.00Hz
Factory Setting: 60.00
01.33 Maximum Output Voltage (Vmax) (Motor 2) Unit: V
Settings 115V/230V series 0.1 to 255.0V Factory Setting: 220.0
460V series 0.1 to 510.0V Factory Setting: 440.0
01.34 Mid-Point Frequency (Fmid) (Motor 2) Unit: Hz
Settings 0.10 to 599.00Hz
Factory Setting: 1.50
01.35 Mid-Point Voltage (Vmid) (Motor 2) Unit: V
Settings 115V/230V series 0.1 to 255.0V Factory Setting: 10.0
460V series 0.1 to 510.0V Factory Setting: 20.0
01.36 Minimum Output Frequency (Fmin) (Motor 2) Unit: Hz
Settings 0.10 to 599.00Hz
Factory Setting: 1.50
01.37 Minimum Output Voltage (Vmin) (Motor 2) Unit: V
Settings 115V/230V series 0.1 to 255.0V Factory Setting: 10.0
460V series 0.1 to 510.0V Factory Setting: 20.0
01.38 Maximum Voltage Frequency (Fbase) (Motor 3) Unit: Hz
Settings 0.10 to 599.00Hz Factory Setting: 60.00
01.39 Maximum Output Voltage (Vmax) (Motor 3) Unit: V
Settings 115V/230V series 0.1 to 255.0V Factory Setting: 220.0
460V series 0.1 to 510.0V Factory Setting: 440.0