Chapter 4 Parameters
4-134
08.28
Output Voltage Limit
Unit: %
Settings 80~150% Factory Setting: 100
This parameter sets the limit for actual output voltage. For constant torque applications, sets
this parameter to high value can lower the load current.
08.29
Special Bit Control Parameter
Factory Setting: 0
Settings Bit0 =1, cancel internal frequency command filter
Bit1 =1, set Pr00-05 to two decimal places
Bit2 =1, enable low voltage LvX fault recording function
In order to let frequency command gently, drive can use frequency command filter but the
response will be slow. If you want the fast response you can set Bit0=1(cancel internal
frequency command filter).
Set Pr08-29=4 (Bit2 =ON) to enable low voltage LvA (430, Lvn (44) and Lvd (45) warning
recording function. Pr08-29 is defined as above.