Chapter 4 Parameters
4-167
Pr.12.22 = [(full scale voltage)/10]*100%.
Example: When using voltmeter with full scale (5V), Pr.12.22 should be set to 5/10*100%=50%. If
Pr.12.21 is set to 0, the output voltage will correspond to the max. output frequency.
12.23
AO2Terminal Analog Signal Mode
Factory Setting: 0
Settings 0 AVO2
1 ACO2 (analog current 0.0 to 20.0mA)
2 ACO2 (analog current 4.0 to 20.0mA)
Besides parameter setting, the voltage/current mode should be used with the switch.
AVI3
ACI2
AVI4
ACI3
AVO1
ACO1
AVO2
ACO2
12.24
AO2 Analog Output Signal
Factory Setting: 0
Settings 0 Analog Frequency
1 Analog Current (0 to 250% rated current)
12.25 AO2 Analog Output Gain Unit: %
Settings 1 to 200% Factory Setting: 100
Setting method for the AO2 is the same as the AO1.
12.26
AUI Analog Input Selection
Factory Setting: 0
Settings 0 No function
1 Source of the 1st frequency
2 Source of the 2nd frequency
12.27 AUI Analog Input Bias Unit: %
Settings 0.00 to 200.00% Factory Setting: 0.00