Chapter 4 Parameters
4-58
Assume that the radius of the 4-pole motor is r and rotation speed is n (rpm).
r
n
Example 1:
Assume that motor speed is 50Hz, the delay time at 50Hz is 2 sec (Pr.01.25=2) and the
deceleration time from 50Hz to 0Hz is 10 seconds.
The rotation speed n = 120 X 50 /4 (rpm/min) = 25 rpm/sec
The revolution numbers = (25 X (2+12))/2 = 175 (revolutions)
f
(Hz)
t
2sec 10sec
50
MI=25
ON
Therefore, the distance = revolution numbers X circumference = 175 X 2 r
It also means that the motor will stop to the original position after 175 circles.
Example 2:
Assume that motor speed is 1.5Hz, the delay time at 10Hz is 10 sec (Pr.01.21=10) and the
deceleration time from 60Hz to 0Hz is 40 seconds.
The delay time at 1.5Hz is 1.5 sec and the deceleration from 1.5Hz to 0Hz is 1 sec.
The rotation speed n = 120 X 1.5 /4 (rpm/min) = 1.5/2 rpm/sec = 0.75 rpm/sec
The revolution numbers = (1.5/2X (1.5+2.5))/2 = 1.5 (revolutions)
MI=25
ON
1.5
1.5sec 1sec
f
(Hz)
Therefore, the distance = revolution numbers X circumference = 1.5 X 2 r
It also means that the motor will stop after running 1.5 circles.
01.26 Maximum Voltage Frequency (Fbase) (Motor 1) Unit: Hz
Settings 0.10 to 599.00Hz
Factory Setting: 60.00
01.27 Maximum Output Voltage (Vmax) (Motor 1) Unit: V
Settings 115V/230V series 0.1 to 255.0V Factory Setting: 220.0