Chapter 4 Parameters
4-27
Group 9 Communication Parameters
Parameter Explanation Settings
Factory
Setting
Custome
r
09.00
Communication
Address
1 to 254 1
09.01 Transmission Speed
0: Baud rate 4800bps
1
1: Baud rate 9600bps
2: Baud rate 19200bps
3: Baud rate 38400bps
09.02
Transmission Fault
Treatment
0: Warn and keep operating
3
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and keep operating
09.03 Time-out Detection
0.1 ~ 120.0 seconds
0.0: Disable
0.0
09.04
Communication
Protocol
0: 7,N,2 (Modbus, ASCII)
0
1: 7,E,1 (Modbus, ASCII)
2: 7,O,1 (Modbus, ASCII)
3: 8,N,2 (Modbus, RTU)
4: 8,E,1 (Modbus, RTU)
5: 8,O,1 (Modbus, RTU)
6: 8,N,1 (Modbus, RTU)
7: 8,E,2 (Modbus, RTU)
8: 8,O,2 (Modbus, RTU)
9: 7,N,1 (Modbus, ASCII)
10: 7,E,2 (Modbus, ASCII)
11: 7,O,2 (Modbus, ASCII)
09.05 Reserved
09.06 Reserved
09.07
Response Delay
Time
0 ~ 200 (unit: 2ms)
1