Chapter 4 Parameters
4-26
Parameter Explanation Settings
Factory
Setting
Custome
r
08.13
Skip Frequency 3
Upper Limit
0.00 to 599.00 Hz
0.00
08.14
Skip Frequency 3
Lower Limit
0.00 to 599.00 Hz
0.00
08.15
Auto Restart After
Fault
0 to 10 (0=disable)
0
08.16
Auto Reset Time at
Restart after Fault
0.1 to 6000 sec
60.0
08.17 Auto Energy Saving
0: Disable
0
1: Enable
08.18 AVR Function
0: AVR function enable
0
1: AVR function disable
2: AVR function disable for decel.
3: AVR function disable for stop
08.19
Software Brake
Level
115V / 230V series: 370.0to 430.0V
380.0
460V series: 740.0 to 860.0V
760.0
08.20
Compensation
Coefficient for Motor
Instability
0.0~5.0
0.0
08.21 OOB Sampling Time
0.1 to 120.0 sec
1.0
08.22
Number of OOB
Sampling Times
00 to 32
20
08.23
OOB Average
Sampling Angle
Read only
#.#
08.24 DEB Function
0: Disable
1: DEB Enable (return after the power
recovery)
0
08.25 DEB Return Time
0 to 25 sec
0
08.26
Speed Search
during Start-up
0: Disable
1: Enable
0
08.27
Speed Search
Frequency during
Start-up
0: By setting frequency
1: By max. operation frequency (Pr.01.00) 0
08.28 Output Voltage Limit
80~150%
100
08.29
Special Bit Control
Parameter
Bit0 =1, cancel internal frequency command
filter.
Bit1 =1, set Pr00-05 to two decimal places.
Bit2 =1, enable low voltage LvX fault recording
function.
0