D-47
Mnemonic Function
SET Latch (ON)
Operand
X0~X17 Y0~Y17 M0~M159 T0~15 C0~C7 D0~D29
--
-- -- --
Explanations:
When the SET command is driven, its specific device is set to be “ON,” which will keep “ON” whether
the SET command is still driven. You can use the RST command to set the device to “OFF”.
Program Example:
Ladder diagram: Command code: Operation:
X0 Y0
Y1
SET
LD X0 Load contact A of X0
ANI Y0 Connect to contact B of Y0 in series
SET Y1 Y1 latch (ON)
Mnemonic Function
RST Clear the contacts or the registers
Operand
X0~X17 Y0~Y17 M0~M159 T0~15 C0~C7 D0~D29
--
--
Explanations:
When the RST command is driven, motion of its specific device is as follows:
Device Status
Y, M Coil and contact will be set to “OFF”.
T, C
Present values of the timer or counter
will be set to 0, and the coil and contact
will be set to “OFF.”
D The content value will be set to 0.
Program Example:
Ladder diagram: Command code: Operation:
X0
Y5
RST
LD X0 Load contact A of X0
RST Y5 Clear contact Y5