EasyManua.ls Logo

Delta VFD-E Series - Page 61

Delta VFD-E Series
435 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Parameters
4-6
Parameter Explanation Settings
Factory
Setting
Customer
01.33
Maximum Output
Voltage (Vmax)
(Motor 2)
115V/230V series: 0.1V to 255.0V 220.0
460V series: 0.1V to 510.0V 440.0
01.34
Mid-Point
Frequency (Fmid)
(Motor 2)
0.10 to 599.00 Hz
1.50
01.35
Mid-Point Voltage
(Vmid) (Motor 2)
115V/230V series: 0.1V to 255.0V 10.0
460V series: 0.1V to 510.0V 20.0
01.36
Minimum Output
Frequency (Fmin)
(Motor 2)
0.10 to 599.00 Hz
1.50
01.37
Minimum Output
Voltage (Vmin)
(Motor 2)
115V/230V series: 0.1V to 255.0V 10.0
460V series: 0.1V to 510.0V 20.0
01.38
Maximum Voltage
Frequency (Fbase)
(Motor 3)
0.10 to 599.00 Hz 60.00
01.39
Maximum Output
Voltage (Vmax)
(Motor 3)
115V/230V series: 0.1V to 255.0V 220.0
460V series: 0.1V to 510.0V 440.0
01.40
Mid-Point
Frequency (Fmid)
(Motor 3)
0.10 to 599.00 Hz
1.50
01.41
Mid-Point Voltage
(Vmid) (Motor 3)
115V/230V series: 0.1V to 255.0V 10.0
460V series: 0.1V to 510.0V 20.0
01.42
Minimum Output
Frequency (Fmin)
(Motor 3)
0.10 to 599.00 Hz
1.50
01.43
Minimum Output
Voltage (Vmin)
(Motor 3)
115V/230V series: 0.1V to 255.0V 10.0
460V series: 0.1V to 510.0V 20.0

Table of Contents