Chapter 4 Parameters
4-9
Parameter Explanation Settings
Factory
Setting
Customer
02.11
Keypad Frequency
Command
0.00 to 599.00Hz
60.00
02.12
Communication
Frequency
Command
0.00 to 599.00Hz
60.00
02.13
The Selections for
Saving Keypad or
Communication
Frequency
Command
0: Save Keypad & Communication
Frequency
1: Save Keypad Frequency only
2: Save Communication Frequency only
0
02.14
Initial Frequency
Selection (for
keypad &
RS485/USB)
0: by Current Freq Command
0
1: by Zero Freq Command
2: Refer to Pr.02-15 to set up
02.15
Initial Frequency Set
point (for keypad &
RS485/USB)
0.00 ~ 599.00Hz
60.00
02.16
Display the Master
Freq Command
Source
Read Only
Bit0=1: by First Freq Source (Pr.02.00)
Bit1=1: by Second Freq Source (Pr.02.09)
Bit2=1: by Multi-input function
Bit3=1: by PLC Freq command (NOT for
VFD*E*C models)
1
02.17
Display the
Operation
Command Source
Read Only
Bit0=1: by Digital Keypad
Bit1=1: by RS485 communication
Bit2=1: by External Terminal 2/3 wire mode
Bit3=1: by Multi-input function
Bit4=1: by PLC Operation Command (NOT
for VFD*E*C models)
Bit5=1: by CANopen communication
4
02.18
Selection of Carrier
Modulation
0: by carrier modulation of load current and
temperature
1: by carrier modulation of load current
0
02.19
Selection of Zero
speed control mode
0: Enter standby mode when zero speed
1: Run DC brake when zero speed(the max.
output voltage *0.05 )
0